Com+ Mechanical designs and installs variable refrigerant flow systems across the NYC metro area, engineering branch-controller layouts, refrigerant piping, and BMS integration around how your building actually runs. From single-floor office fit-outs to multi-riser portfolios, we deliver simultaneous heating and cooling, tenant-level zoning, and the documentation your commissioning and Local Law 97 reporting require. One condensing platform, dozens of independently controlled zones, installed to manufacturer spec.
VRF carries compressor oil with the refrigerant. On high-lift vertical runs without correctly sized oil-return traps and double risers, oil pools in the piping, starves the inverter compressor of lubrication, and triggers premature failure. We design riser geometry and trap spacing to the manufacturer's maximum elevation and length limits.
Refrigerant piping that exceeds equivalent-length limits or uses the wrong diameter at each branch causes capacity loss, poor oil return, and nuisance faults. We size every segment off the manufacturer's piping software, not field guesswork, and pressure-test to spec before insulation.
VRF systems hold large charges and are intolerant of moisture and non-condensables. A rushed single evacuation leaves moisture that forms acids, corrodes the compressor, and clogs electronic expansion valves. We triple-evacuate to 500 microns, hold vacuum, and weigh in the additional charge calculated from total line length.
Every indoor unit and branch box carries a network address on the control bus. Duplicate or missing addresses leave zones unresponsive or cross-controlled. We commission and verify every address, confirm communication end to end, and document the as-built network map.
Large refrigerant charges in small or below-grade rooms can exceed the refrigerant concentration limit if a line fails. Installs that ignore this skip required leak detection and create a life-safety and code problem. We calculate concentration per smallest occupied space and add detection and alarms where required.
Cassettes and ducted fan coils mounted above ceilings rely on condensate pumps and properly pitched drains. Skimped condensate design produces ceiling leaks and tenant damage once the system runs in cooling. We install pumps, traps, float safety switches, and secondary drainage on every applicable unit.
A variable refrigerant flow system is only as good as its design and installation. Unlike a packaged rooftop unit you set and forget, VRF is a distributed network: inverter-driven condensing units feeding refrigerant through branch selector boxes and electronic expansion valves to fan coils in every zone, all coordinated over a manufacturer control bus. Get the line-set sizing, oil-return strategy, or refrigerant charge wrong and you trade away the efficiency that justified the system in the first place. Com+ Mechanical installs VRF and VRV systems for offices, medical suites, retail, schools, multifamily, and mixed-use buildings throughout the five boroughs, Nassau, Westchester, northern New Jersey, and Stamford. We size to a real block-load calculation, lay out piping for proper trap and oil return, pressure-test and triple-evacuate before charging, and commission every indoor unit and address on the bus. The result is a system that delivers simultaneous heating and cooling across tenants, throttles to part load instead of cycling, and gives building engineers granular control and trend data they can actually use for Local Law 97 compliance.
From call to comfort in 4 easy steps
We walk the building, review architectural and electrical drawings, and run a block-load plus zone-by-zone calculation. We confirm electrical service, riser pathways, condensing-unit placement, and refrigerant concentration limits before any equipment is selected.
We engineer the condensing-unit, branch-controller, and indoor-unit layout, size every refrigerant line segment in manufacturer piping software, and produce submittals, a scoped Custom Quote, and a phasing plan that keeps tenants conditioned during the changeover.
Crews set condensing units, run and braze ACR copper under nitrogen, mount indoor units and branch boxes, and pull control and power wiring. We nitrogen pressure-test, triple-evacuate to 500 microns, and weigh in the calculated charge.
We address and verify every unit on the bus, set up the central controller and schedules, integrate to your BMS, confirm heating, cooling, and heat-recovery modes, and hand over a commissioning report, as-builts, and a maintenance plan.
A two-pipe configuration where all connected indoor units operate in the same mode at a given time, either heating or cooling. The most cost-effective VRF option, well suited to buildings or tenants whose zones share a load direction, such as a single-exposure floor plate.
A three-pipe system with branch selector boxes that let some zones heat while others cool at the same time, recovering heat rejected by cooling zones to serve heating zones. Maximum efficiency for buildings with mixed exposures, varied tenant uses, or simultaneous perimeter heating and core cooling.
A configuration that rejects and absorbs heat through a building water loop instead of air-cooled condensers. A strong fit for high-rises with limited rooftop or facade space for outdoor units, or buildings already running a condenser-water or geothermal loop.
We focus on commercial variable refrigerant flow for NYC-metro buildings, not residential one-offs. We understand multi-riser layouts, occupied-building phasing, and the difference heat-recovery design makes to a portfolio's operating cost.
Line-set sizing from manufacturer software, triple evacuation, weighed-in charge, and full bus commissioning. We install to the spec that protects the equipment warranty and the efficiency you paid for.
We integrate VRF to your building automation system over BACnet or LonWorks and deliver the trend data and documentation that support Local Law 97 reporting and tenant submetering across your buildings.
One contractor for VRF across your buildings, with 24/7 emergency response after installation so a fault on the control bus or a compressor lockout gets attention day or night.
No fees. No surprises. Just honest service.
Engineering-first engagement to confirm whether VRF is the right system and how it should be configured before any equipment is ordered.
Complete design-build installation of the condensing units, branch controllers, indoor units, piping, controls, and BMS integration, commissioned and documented.
Scheduled preventive maintenance to protect the warranty, hold efficiency, and catch refrigerant, oil-return, and control faults before they cause downtime.
All VRF pricing is scoped after an on-site assessment and load calculation; final cost reflects building load, riser layout, indoor-unit count, configuration, and BMS scope.
Business+ plans start at $499/year — includes 2 rtu tune-ups, 10% off all services, and priority scheduling.
Factory-trained technicians for all major HVAC manufacturers









Don't see your brand? We service all major manufacturers! Call us to confirm.
Fast, reliable service in your neighborhood
Get answers to common questions about our services
It depends on your load profile. Heat-pump VRF heats or cools all connected zones in one mode at a time and costs less. Heat-recovery VRF uses branch selector boxes so some zones heat while others cool simultaneously, capturing rejected heat and moving it where it is needed. Buildings with a sunny perimeter and a cold core, or mixed tenant uses, usually justify heat recovery on operating-cost savings. We model both during the design assessment and recommend the right fit. Call (332) 600-4640 to start.
Yes. VRF's distributed, zone-by-zone nature makes phased installation practical. We sequence riser work, branch boxes, and indoor units floor by floor or tenant by tenant, keeping conditioned space online while we cut over zones. We build the phasing plan into the proposal so building management and tenants know the schedule in advance.
Yes. We install and maintain VRF for property managers and owners running multiple buildings across the NYC metro area, standardizing on a manufacturer platform where it makes sense and consolidating commissioning data and maintenance reporting so your team sees every building's systems in one place.
VRF reduces energy use through inverter modulation, zone-level control that idles unoccupied space, and heat recovery that reuses rejected heat instead of generating new heating energy. Just as important for Local Law 97, the system reports granular runtime and energy data over your BMS, giving you defensible trend data to document performance and target further reductions. We set up that integration as part of commissioning.
VRF needs scheduled service on every indoor unit (coils, filters, condensate drains and pumps) plus periodic verification of refrigerant charge, oil return, inverter compressor performance, electronic expansion valve operation, and control-bus health. Skipped maintenance shows up as efficiency loss and eventually compressor or EXV faults. Our maintenance agreement covers these tasks and keeps the equipment warranty intact.
Yes. Once your VRF system is in service we provide 24/7 emergency response for control-bus faults, compressor lockouts, refrigerant alarms, and no-heat or no-cool conditions, so a problem in one zone or across the system gets a technician's attention any time.
Manage a building we've serviced? A quick review helps other NYC property managers and building owners find us.
5 stars • 500+ reviews
Our businesses' top picks for heating, cooling & air quality
Equipment services, industry expertise, NYC compliance, and the metro areas we cover.
If you are weighing VRF for zoned efficiency, start with engineering, not a catalog number. Com+ Mechanical will assess your building, run the load, recommend the right configuration, and deliver an installation commissioned to manufacturer spec and integrated to your BMS. Serving property managers, owners, and facility teams across the five boroughs, Nassau, Westchester, northern New Jersey, and Stamford. Call (332) 600-4640 to schedule a VRF design consultation.
Request a VRF Design Consultation